| Aspect | RS-232 | RS-485 | RS-422 |
|---|---|---|---|
| Topology | Point-to-point; one driver, one receiver | Multi-drop; many nodes on one twisted pair | One driver to up to ten receivers |
| Distance | Up to about 15 m at full rate | Up to about 1,200 m at low rate | Up to about 1,200 m |
| Noise immunity | Single-ended; weaker against ground noise | Differential; strong common-mode noise rejection | Differential; strong noise rejection |
| Data rate | Lower, short cables and legacy links | High over short distance, lower over long lines | High over short to medium lines |
| Best fit | Short links and legacy equipment | Industrial multi-node buses and long runs | One-to-many balanced links |
How to decide
RS-232 suits short, single-device links such as legacy test and console ports. RS-485 is the standard industrial multi-drop bus for PLCs, sensors and drives over long noisy runs. RS-422 sits between them: a balanced one-to-many link where the bus does not need bidirectional multi-drop. Check the required nodes, cable length and baud rate before locking the transceiver.